Skip to menu

MRBAS

CES

CES
Full Lighting Controls
Sensor & Switches
Overview
CES series PHOTO SENSORs are largely divided into four types. It is for indoor, outdoor, mining windows, and atrium. These sensors are three-wire analog optical sensors that provide illumination input.
Indoor sensors are used in offices, and outdoor sensors detect light for signage and field lighting control. The atrium sensor measures light in the lobby, and the light-mining sensor detects ambient light available in the warehouse light-mining window. These sensors are connected to the sensor input terminal of the ELC system to measure illumination in the lighting control system, set illumination in the program, and turn on the relevant lamp relay by the set illumination.
Main Feature
Measurement Range : 0 - 7,500fc(0 - 80,000Lux)
Output : 5 - 10V
Fixed Response Time
Indoor sensor adhesive ceiling mount
UL916 Registered Products
Application
Most of these illumination control light sensors are installed indoors in the window area.
Multiple lighting control relays are controlled with illuminance sensed by one illuminance sensor.
Control by illumination sensor is carried out mainly in the window area.
This illumination sensor can be measured, and the illumination value is displayed on the central monitoring board PC, and the illumination value is monitored and set according to the illumination in the window area to control the corresponding illumination relay.
Specification
Input Voltage: 5, 10, 12, 24VDC
Power Consumption: 113mW
Low Output: 0 or 1VDC
High Output: 5 or 10VDC
Photodiode: Blue Enhanced
Fixed signal range: 0-5, 1-5, 0-10, 1-10
Gain Adjustment: 25 Turn Potentiometer
Time Response: Fixed 10 seconds Full Range
Deviation range: 12% (Repeatability: +/- 0.5%, Linearity: 2%, Temp: +/- 10%)
Ambient temperature: - 20 to 75℃
Wiring: Red: Input Voltage, Yellow: Signal Voltage, Black: Return
Dimension of Layout
Connection Diagram